The GYR Node Series (Green-Yellow-Red Nodes) are visual/electrical units that tell the hydraulic system/fluid condition at a glance using the universal color meanings of Green, Yellow, and Red.

The GYR Nodes are small, compact interfaces that can be added to any of our sensors to display a status light via a 4-20 mA signal. These units can stand alone or pass through data using the 4-20 mA signal from the host sensor to a higher source.
Unit of Measure

Specifications

Series

N/A GYR

Type

N/A Green Yellow Red Node

Ouput Data Signal

N/A 4 to 20mA

Power Requirements

N/A Uses External Power (12 V - 38 V DC at 2 amps)

Input Data Signal

N/A 4 to 20mA

Sensor Type (One per Node)

N/A Pressure Sensor - EDS 8476-2-0500-400

Warning Indication

N/A Yellow Set to 60%; Red Set to 80% (percentage of full range)

Application

Application

N/A
  • Pulp & Paper
  • Power Generation
  • Industrial Hydraulics
  • Wind Power
  • Steel Making
  • Off Road Mining & Construction
  • Marine

Features and Benefits

Features and Benefits

N/A
  • Prominent LED lights for increased system status visibility
  • Customizable trigger points
    • GREEN Light = Safe; Operating Normally
    • YELLOW Light = Caution or Warning
    • RED Light = Fault State;
    Exceeded set parameters
  • Quickly connects to any 4-20mA sensor to provide visual status of sensor
  • Easily integrated to a Condition Sensor Interface for data collection or transfer of customer’s data control system
  • Web Interface (OTA, Over-The-Air) offers data recording. The interface can be accessed on any Wi-Fi enabled device
  • Timer function available for any user and is adjustable on the web interface for the customer
  • IP67 Rated

Additional Information

Additional Information

N/A The NODE can be easily connected to a Condition Sensor interface (e.g. CSI-C-11) or a customer’s data control system for data collection for predictive or preventive maintenance strategies. Data collection can also be achieved via included Web Interface (OTA, Over-the-Air) which offers data recording. The interface can be accessed on any WiFi enabled device such as a PC, Cell phone, tablet, etc.Green/Yellow/Red Lights are programmed for specific sensor function. The GYR Node can scale any 4-20 mA signal to appropriately display proportional indication lights.

Included timer function will allow the user to see how long the system has been in operation. For example, when used with a differential pressure clogging indicator, the user will be able to change element based on time in service. The timer function is adjustable on the web interface which can be accessed on any WiFi enabled device.